HVAC Việt Nam

Daikin VRV IV RYYQ-T – RYYQ54T7Y1B, RYYQ50T7Y1B, RYYQ24T7Y1B

RYYQ-T

RYYQ54T7Y1B RYYQ50T7Y1B RYYQ24T7Y1B
System Outdoor unit module 1 RYMQ18T7Y1B RYMQ16T7Y1B RYMQ8T7Y1B
Outdoor unit module 2 RYMQ18T7Y1B RYMQ16T7Y1B RYMQ16T7Y1B
Outdoor unit module 3 RYMQ18T7Y1B RYMQ18T7Y1B
Cooling capacity Nom. kW 150.0 (1) 140.0 (1) 67.4 (1)
Heating capacity Nom. kW 168.0 (2) 156.0 (2) 75.0 (2)
Power input – 50Hz Cooling Nom. kW 44.1 (1) 40.7 (1) 18.2 (1)
Heating Nom. kW 43.2 (2) 40.0 (2) 18.3 (2)
EER 3.40 (1) 3.44 (1) 3.70 (1)
COP 3.89 (2) 3.90 (2) 4.10 (2)
ESEER 4.97 (17)
6.38 (18)
5.02 (17)
6.46 (18)
5.42 (17)
6.81 (18)
Capacity range HP 54 50 24
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3)
Indoor index connection Min. 675 625 300
Nom. 1,350 1,250 600
Max. 1,755 1,625 780
Dimensions Unit Height mm
Width mm
Depth mm
Weight Unit kg
Fan Air flow rate Cooling Nom. m³/min
External static pressure Max. Pa
Compressor Type
Operation range Cooling Max. °CDB
Heating Min. °CWB
Max. °CWB
Sound power level Cooling Nom. dBA
Sound pressure level Cooling Nom. dBA
Refrigerant Type
Piping connections Liquid Type
OD mm 19.1 19.1 15.9
Gas Type
OD mm 41.3 41.3 34.9
Heat insulation Liquid, gas and equalizing pipe Liquid, gas and equalizing pipe Liquid, gas and equalizing pipe
Total piping length System Actual m 1,000 (10) 1,000 (10) 1,000 (10)
Level difference OU – IU Outdoor unit in highest position m 90 (10) 90 (10) 90 (10)
Indoor unit in highest position m 90 (10) 90 (10) 90 (10)
IU – IU Max. m 30 (10) 30 (10) 30 (10)
Standard Accessories Item
Item
Power supply Name Y1 Y1 Y1
Phase 3N~ 3N~ 3N~
Frequency Hz 50 50 50
Voltage V 380-415 380-415 380-415
Notes Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50%
RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.
Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current. Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current. Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
Refer to refrigerant pipe selection or installation manual Refer to refrigerant pipe selection or installation manual Refer to refrigerant pipe selection or installation manual
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and
Short-circuit power Short-circuit power Short-circuit power
system impedance system impedance system impedance
Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534 Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534 Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation) The AUTOMATIC SEER value corresponds with normal VRV4 Heat Pump operation, taking into account advanced energy saving operation functionality ( variable refrigerant temperature control operation)
Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account. Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account. Sound values are theoretical values based on sound results of individual installed units. Possible deviations due to variety of installation patterns are not taken into account.
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
Soundpressure system [dBA] = 10*log[10^(A/10)
10^(B/10)
10^(C/10)] , with Unit A = A dBA, Unit B = B dBA, Unit C = C dBA
Exit mobile version