HVAC Việt Nam

Daikin VRV IV RYYQ-T – RYYQ14T7Y1B, RYYQ16T7Y1B, RYYQ18T7Y1B

RYYQ14 20T - HVAC Việt Nam

RYYQ-T

RYYQ14T7Y1B RYYQ16T7Y1B RYYQ18T7Y1B
System Outdoor unit module 1
Outdoor unit module 2
Outdoor unit module 3
Cooling capacity Nom. kW 40.0 (1) 45.0 (1) 50.0 (1)
Heating capacity Nom. kW 45.0 (2) 50.0 (2) 56.0 (2)
Power input – 50Hz Cooling Nom. kW 11.0 (1) 13.0 (1) 14.7 (1)
Heating Nom. kW 11.2 (2) 12.8 (2) 14.4 (2)
EER 3.64 (1) 3.46 (1) 3.40 (1)
COP 4.02 (2) 3.91 (2) 3.89 (2)
ESEER 5.31 (24)
6.83 (25)
5.05 (24)
6.50 (25)
4.97 (24)
6.38 (25)
Capacity range HP 14 16 18
Maximum number of connectable indoor units 64 (3) 64 (3) 64 (3)
Indoor index connection Min. 175 200 225
Nom. 350 400 450
Max. 455 520 585
Dimensions Unit Height mm 1,685 1,685 1,685
Width mm 1,240 1,240 1,240
Depth mm 765 765 765
Weight Unit kg 364 364 398
Fan Air flow rate Cooling Nom. m³/min 223 260 251
External static pressure Max. Pa 78 78 78
Compressor Type Hermetically sealed scroll compressor Hermetically sealed scroll compressor Hermetically sealed scroll compressor
Operation range Cooling Max. °CDB 43 43 43
Heating Min. °CWB -20 -20 -20
Max. °CWB 15.5 15.5 15.5
Sound power level Cooling Nom. dBA 81 86 86
Sound pressure level Cooling Nom. dBA 61 64 65
Refrigerant Type R-410A R-410A R-410A
Piping connections Liquid Type Braze connection Braze connection Braze connection
OD mm 12.7 12.7 15.9
Gas Type Braze connection Braze connection Braze connection
OD mm 28.6 28.6 28.6
Heat insulation Both liquid and gas pipes Both liquid and gas pipes Both liquid and gas pipes
Total piping length System Actual m 1,000 (7) 1,000 (7) 1,000 (7)
Level difference OU – IU Outdoor unit in highest position m 90 (7) 90 (7) 90 (7)
Indoor unit in highest position m 90 (7) 90 (7) 90 (7)
IU – IU Max. m 30 (7) 30 (7) 30 (7)
Standard Accessories Item Installation and operation manual Installation and operation manual Installation and operation manual
Item Connection pipes Connection pipes Connection pipes
Power supply Name Y1 Y1 Y1
Phase 3N~ 3N~ 3N~
Frequency Hz 50 50 50
Voltage V 380-415 380-415 380-415
Notes Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 5m; level difference: 0m
Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 5m; level difference: 0m
Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50% Actual number of connectable indoor units depends on the indoor unit type (VRV indoor, Hydrobox, RA indoor, etc.) and the connection ratio restriction for the system (50%
For more details on operation range see TW drawing For more details on operation range see TW drawing For more details on operation range see TW drawing
Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
Refer to refrigerant pipe selection or installation manual Refer to refrigerant pipe selection or installation manual Refer to refrigerant pipe selection or installation manual
For more details on standard accessories refer to Installation/operation manual For more details on standard accessories refer to Installation/operation manual For more details on standard accessories refer to Installation/operation manual
RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB
MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current. MSC means the maximum current during start up of the compressor. VRV IV uses only inverter compressors. Starting current is always ≤ max. running current.
Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current. Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current. Select wire size based on the value of MCA. The MCA can be regarded as the maximum running current.
MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker).
TOCA means the total value of each OC set. TOCA means the total value of each OC set. TOCA means the total value of each OC set.
FLA means the nominal running current of the fan FLA means the nominal running current of the fan FLA means the nominal running current of the fan
In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value. In accordance with EN/IEC 61000-3-11, respectively EN/IEC 61000-3-12, it may be necessary to consult the distribution network operator to ensure that the equipment is connected only to a supply with Zsys ≤ Zmax, respectively Ssc ≥ minimum Ssc value.
European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A. European/International Technical Standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated current ≤ 75A.
European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low-voltage systems with input current >16A and
Short-circuit power Short-circuit power Short-circuit power
system impedance system impedance system impedance
Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534 Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534 Multi combination (22~54HP) data is corresponding with the standard multi combination as mentioned on 3D079534
Sound power level is an absolute value that a sound source generates. Sound power level is an absolute value that a sound source generates. Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings. Sound pressure level is a relative value, depending on the distance and acoustic environment. For more details, please refer to the sound level drawings.
Sound values are measured in a semi-anechoic room. Sound values are measured in a semi-anechoic room. Sound values are measured in a semi-anechoic room.
The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality The STANDARD ESEER value corresponds with normal VRV4 Heat Pump operation, not taking into account advanced energy saving operation functionality
Exit mobile version